Chilled water riser RAMS

A wet riser full of glycol is not ‘pipework’. A generic M&E RAMS that never mentions drain-down volume, drip into a live office or same-visit fire-stopping will fail the clerk of works.

Typical scope

  • Drain volume agreed
  • Floors below briefed
  • Pressure test before lagging
  • Vapour-tight insulation
  • Fire-stop same visit
  • Riser locked

Quick answer

A chilled-water riser RAMS covers installing or altering CHW pipework in a vertical riser. Isolation of a live system, water over occupied floors, insulation of cold pipe and fire-stopping of the riser are the core.

Primary topic: chilled water riser rams. UK contractors — review every document before you issue it. SafeForJob does not replace competent judgement or HSE guidance.

What usually goes wrong

These are the operational gaps that make generic Word RAMS fail on the next site.

  • LTHW RAMS reused

    No vapour seal, wrong fluid.

  • Drained into the lift lobby

    Flood.

  • Penetration left for the fire-stopper ‘next week’

    Strategy open.

Example

CHW riser alteration on a live office

Built from one job description. You review and adjust every item before issuing it.

Job description

Alter the CHW riser at Greyfriars House, Leicester, Saturday. Drain to a 1000 L IBC in the basement, floors 2–4 briefed, pressure test before lagging, vapour seal, fire-stop each slab before 18:00, riser locked.

Activities identified

  • General site work

Method (4 steps)

  1. 1.Arrive and sign in. Arrive at Riser C, Greyfriars House, Leicester, report to the Greyfriars FM site contact, sign in and complete any site induction.
  2. 2.Brief the team. Brief all operatives on this RAMS, the COSHH assessments and the emergency arrangements. Record attendance.
  3. 3.Clear up and remove waste. Clear the work area, remove waste from site (including recovered refrigerant and hazardous waste) and leave the area safe.
  4. 4.Hand over and sign out. Hand over to the Greyfriars FM site contact, report anything outstanding and sign out.

Main risks (0 in total)

What to get right on this document

Glycol is COSHH and pollution

Spill and volume.

Test then lag

Find the leak now.

Close the compartment

Fire-stop as you go.

What this document has to cover

A wet riser full of glycol is not ‘pipework’. A generic M&E RAMS that never mentions drain-down volume, drip into a live office or same-visit fire-stopping will fail the clerk of works.

A chilled water riser rams only holds up if it names the site, the people at risk, the critical control, and the order of work. Principal contractors reject paragraphs that could apply to any job of this type.

Typical hazards to assess on this job

  • Water or glycol flood onto occupied floors
  • Electric shock if you clip a live electrical riser
  • Falls in a narrow locked riser
  • Manual handling of long pipe in a stair
  • Condensation and mould if insulation is skipped
  • Fire strategy broken by an open riser cupboard

Likelihood and severity change with occupancy, access, weather and other trades. Copying last month’s scores without looking at this site is how people get hurt.

A method sequence that actually protects people

Write the sequence so the critical control cannot be skipped. If isolation, edge protection or service location is the difference between safe and unsafe, it belongs before the work step — not in a general ‘PPE will be worn’ line.

  • Agree isolation, drain volume and a spill route that is not the lift lobby
  • Lock the riser; exclude the floors you could wet
  • Cut in, fit, pressure-test before insulation hides the joint
  • Insulate vapour-tight; fire-stop every slab the same visit
  • Refill, vent, label
  • Do not leave the riser unlocked or an open penetration overnight

Occupancy and other people

Offices below will claim for a stained ceiling. Write which floors are told, where the drain lands, and that a failed joint is a stop.

Substances and COSHH

An SDS is an input, not a COSHH assessment. If these substances appear on the job, attach assessments that describe quantity, duration, who is exposed and the controls you will actually use:

  • Glycol / inhibited CHW
  • Insulation adhesives and vapour tape
  • Jointing compounds

How SafeForJob helps

  • Describe this job in plain English and get suggested activities, risks and method steps
  • Edit every line before you download or issue
  • Reuse a previous RAMS and catch old client or site names
  • Attach or create COSHH assessments where hazardous substances appear

What this page is not

This page is not HSE approval, legal advice or a substitute for competent judgement. It helps you draft a clearer chilled water riser rams document for a named job. You remain responsible for reviewing and issuing it.

Related reading

See what a RAMS is, the free RAMS generator, and HSE guidance on managing risks.

Related pages

All rams by job · RAMS by trade · Free RAMS generator

Questions

Is glycol just water?
No — COSHH, slip and a pollution incident if it hits a drain.
Can I use the LTHW RAMS?
Hot water is a burn risk; CHW is vapour and glycol. Write this one.
Who owns the drain-down?
The person who runs that CHW circuit — write them, because they own the volume and the refill.
Asbestos in old lagging?
Treat unknown lagging as a stop until it is sampled — chilled risers in 1970s offices often are.