Skip to content
SafeForJob

RAMS by job · UK

Calorifier replacement RAMS

A calorifier is a heavy, dirty, hot store — not a combi swap. A boiler RAMS that never mentions drain temperature, sludge as waste or how you keep a ward in hot water will fail estates.

Typical scope

  • Outage and temporary HWS
  • Cooled drain
  • Lift plan
  • Sludge as waste
  • Commission to the written scheme
  • Dutyholder records

Quick answer

A calorifier replacement RAMS covers isolating, draining, lifting out and installing a hot-water storage vessel. Stored hot water, Legionella of the old vessel, the lift and the building that still wants hot water are the critical harms.

Primary topic: calorifier replacement rams. UK contractors — review every document before you issue it. SafeForJob does not replace competent judgement or HSE guidance.

What usually goes wrong

These are the operational gaps that make generic Word RAMS fail on the next site.

  • Cylinder RAMS reused

    Wrong volume, no scheme.

  • Drained boiling into a corridor

    Scald.

  • Old vessel left open in the yard

    Hygiene and a confined space for fauna.

Example

Calorifier swap in a leisure centre

Built from one job description. You review and adjust every item before issuing it.

Job description

Replace calorifier C1 at Victoria Baths, Stockport. Monday shutdown, primary cooled, drain to the foul via a tun dish, hiab through the yard, sludge sampled, pasteurise to the written scheme, pool showers signed until 16:00.

Activities identified

  • General site work
  • Manual handling
  • Lifting operations
  • Plumbing and heating systems
  • Outdoor or exposed work

Method (10 steps)

  1. 1.Arrive and sign in. Arrive at Victoria Baths, Stockport, report to the Victoria Baths Trust site contact, sign in and complete any site induction.
  2. 2.Brief the team. Brief all operatives on this RAMS, the COSHH assessments and the emergency arrangements. Record attendance.
  3. 3.Isolate and drain down. Isolate the water/heating supply, allow to cool and drain down the affected section. Confirm isolation before breaking into pipework.
  4. 4.Carry out the lift. Carry out lifts to the lift plan, with the exclusion zone in place and a trained slinger/signaller directing.
  5. 5.Disconnect and remove existing equipment. Disconnect and remove the existing equipment. Lower or carry it using mechanical aids or team lifts as planned.
  6. 6.Install new equipment. Position and fix the new equipment to the manufacturer's instructions.
  7. 7.Install pipework. Install and connect pipework. Use press-fit or mechanical joints in place of hot works where possible.
  8. 8.Test and commission. Test and commission the installation. Record results.
  9. 9.Clear up and remove waste. Clear the work area, remove waste from site (including recovered refrigerant and hazardous waste) and leave the area safe.
  10. 10.Hand over and sign out. Hand over to the Victoria Baths Trust site contact, report anything outstanding and sign out.

Main risks (5 in total)

Manual handling

Residual Medium

Who: Operatives

  • Use mechanical aids (trolleys, sack trucks, hoists) for heavy items
  • Team lifts for items too heavy or awkward for one person
  • Route planned and cleared before moving items
  • Operatives trained in safe lifting techniques
  • Gloves with good grip and safety footwear

Lifting operations

Residual Medium

Who: Operatives, public, other trades

  • Lift planned by a competent person; lift plan in place
  • Lifting equipment and accessories have current LOLER thorough examination
  • Exclusion zone below the lift; nobody under suspended loads
  • Trained slinger/signaller directs the lift
  • Lifts stopped in high winds

Hot water, hot surfaces and flooding

Residual Low

Who: Operatives, occupants

  • System isolated, allowed to cool and drained down before work
  • Isolation valves identified and tested before breaking into pipework
  • Drip trays, buckets and wet vac available
  • Gloves when handling recently isolated pipework

Stored pressure

Residual Low

Who: Engineers

  • Systems depressurised and drained down before breaking into pipework
  • Gauges, hoses and valves inspected and rated for the system pressure
  • Cylinders secured upright and transported with valves protected
  • Eye protection worn when connecting or venting

+ 1 more risks in the full RAMS.

What to get right on this document

Cool then drain

Temperature is a control.

The scheme owns restart

Pasteurise as written.

Sludge is waste

Not a yard puddle.

What this document has to cover

A calorifier is a heavy, dirty, hot store — not a combi swap. A boiler RAMS that never mentions drain temperature, sludge as waste or how you keep a ward in hot water will fail estates.

A calorifier replacement rams only holds up if it names the site, the people at risk, the critical control, and the order of work. Principal contractors reject paragraphs that could apply to any job of this type.

Typical hazards to assess on this job

  • Scald from a drain that was never cooled
  • Dropped vessel in a plant room or through a hatch
  • Legionella and biofilm in the old calorifier
  • Electric shock or steam on still-live primary
  • Manual handling of insulation and anodes
  • Occupants without hot water and no temporary provision

Likelihood and severity change with occupancy, access, weather and other trades. Copying last month’s scores without looking at this site is how people get hurt.

A method sequence that actually protects people

Write the sequence so the critical control cannot be skipped. If isolation, edge protection or service location is the difference between safe and unsafe, it belongs before the work step — not in a general ‘PPE will be worn’ line.

  • Agree the outage and any temporary hot water with the dutyholder
  • Isolate primary and secondary; cool, then drain to a safe route — not a floor gully that scalds a corridor
  • Lift out; bag sludge as the waste characterisation requires
  • Land the new vessel, reconnect, fill, vent
  • Pasteurise or commission to the written scheme
  • Hand over anode, insulation and the scheme records

Occupancy and other people

Care homes and sports centres still need showers. Write the temporary arrangement and who is told before the store goes cold.

Substances and COSHH

An SDS is an input, not a COSHH assessment. If these substances appear on the job, attach assessments that describe quantity, duration, who is exposed and the controls you will actually use:

  • Stored hot water and sludge (characterise)
  • Insulation fibres
  • Disinfection chemicals if pasteurising

How SafeForJob helps

  • Describe this job in plain English and get suggested activities, risks and method steps
  • Edit every line before you download or issue
  • Reuse a previous RAMS and catch old client or site names
  • Attach or create COSHH assessments where hazardous substances appear

What this page is not

This page is not HSE approval, legal advice or a substitute for competent judgement. It helps you draft a clearer calorifier replacement rams document for a named job. You remain responsible for reviewing and issuing it.

Related reading

See what a RAMS is, the free RAMS generator, and HSE guidance on managing risks.

Related pages

All rams by job · RAMS by trade · Free RAMS generator

Questions

Is this the same as an unvented cylinder?
Domestic unvented is a different package. This is a commercial store and a written scheme.
Do I always pasteurise?
Follow the scheme — this page does not invent a temperature.
Can AI issue the hygiene record?
A tool can draft the RAMS. A person issues the scheme record.
Confined entry to the old vessel?
If anyone enters, attach a confined-space plan — do not crawl in on this RAMS.