Plate heat exchanger RAMS

A PHE is two fluids one gasket apart. A valve-replacement RAMS that never mentions draining both sides, scald or how you stop Legionella on a DHW exchanger will fail.

Typical scope

  • Both sides isolated and cooled
  • Drain labelled by circuit
  • Manufacturer tension method
  • Torque sequence
  • Two-side pressure test
  • DHW hygiene if applicable

Quick answer

A plate-heat-exchanger RAMS covers installing or stripping a PHE on LTHW, CHW or DHW. Isolation of two circuits, hot water, gasket chemicals and a lift in a plant room are the critical controls.

Primary topic: plate heat exchanger rams. UK contractors — review every document before you issue it. SafeForJob does not replace competent judgement or HSE guidance.

What usually goes wrong

These are the operational gaps that make generic Word RAMS fail on the next site.

  • Valve RAMS reused

    One drain, no plate pack.

  • Opened under spring

    Crush.

  • CIP into a kitchen tap

    Chemical in drinking water.

Example

DHW plate pack service in a hotel energy centre

Built from one job description. You review and adjust every item before issuing it.

Job description

Open and re-gasket the DHW PHE at Harbourview Hotel, Scarborough. Both sides cooled, drains labelled, manufacturer tension sequence, CIP with the named acid, rinse to foul only, pasteurise to the written scheme before guest showers reopen.

Activities identified

  • General site work
  • Occupied premises or public areas
  • Plumbing and heating systems

Method (8 steps)

  1. 1.Arrive and sign in. Arrive at Energy centre, Harbourview Hotel, Scarborough, report to the Harbourview Hotel site contact, sign in and complete any site induction.
  2. 2.Brief the team. Brief all operatives on this RAMS, the COSHH assessments and the emergency arrangements. Record attendance.
  3. 3.Set up the work area. Set up barriers and signage around the work area and keep it clear of other people.
  4. 4.Isolate and drain down. Isolate the water/heating supply, allow to cool and drain down the affected section. Confirm isolation before breaking into pipework.
  5. 5.Install pipework. Install and connect pipework. Use press-fit or mechanical joints in place of hot works where possible.
  6. 6.Test and commission. Test and commission the installation. Record results.
  7. 7.Clear up and remove waste. Clear the work area, remove waste from site (including recovered refrigerant and hazardous waste) and leave the area safe.
  8. 8.Hand over and sign out. Hand over to the Harbourview Hotel site contact, report anything outstanding and sign out.

Main risks (3 in total)

Members of the public and building occupants

Residual Low

Who: Public, customers, staff, residents

  • Work area segregated with barriers and clear signage
  • Work timed for quieter periods where possible, agreed with the site
  • Tools and materials never left unattended in public areas
  • Site contact informed of work areas and any disruption

Hot water, hot surfaces and flooding

Residual Low

Who: Operatives, occupants

  • System isolated, allowed to cool and drained down before work
  • Isolation valves identified and tested before breaking into pipework
  • Drip trays, buckets and wet vac available
  • Gloves when handling recently isolated pipework

Stored pressure

Residual Low

Who: Engineers

  • Systems depressurised and drained down before breaking into pipework
  • Gauges, hoses and valves inspected and rated for the system pressure
  • Cylinders secured upright and transported with valves protected
  • Eye protection worn when connecting or venting

What to get right on this document

Two circuits, two drains

Label them.

Tension is a method

Not a long bar.

DHW is hygiene

Scheme, not a wipe.

What this document has to cover

A PHE is two fluids one gasket apart. A valve-replacement RAMS that never mentions draining both sides, scald or how you stop Legionella on a DHW exchanger will fail.

A plate heat exchanger rams only holds up if it names the site, the people at risk, the critical control, and the order of work. Principal contractors reject paragraphs that could apply to any job of this type.

Typical hazards to assess on this job

  • Scald from a primary that was not cooled
  • Flood from two circuits opened at once
  • Crushing when opening a plate pack under spring
  • Manual handling of a packed frame
  • Chemicals from a CIP clean
  • DHW side hygiene if plates are fouled

Likelihood and severity change with occupancy, access, weather and other trades. Copying last month’s scores without looking at this site is how people get hurt.

A method sequence that actually protects people

Write the sequence so the critical control cannot be skipped. If isolation, edge protection or service location is the difference between safe and unsafe, it belongs before the work step — not in a general ‘PPE will be worn’ line.

  • Isolate and cool both circuits; drain to labelled containers — not a shared bucket
  • Relieve plate-pack tension to the manufacturer’s method before a spanner comes out
  • Lift or open; inspect gaskets; do not mix plates from another duty
  • Reassemble to the specified torque sequence; pressure-test both sides
  • CIP only with the named chemical and a rinse that cannot enter a drinking outlet
  • Hand over duty temperatures and the DHW hygiene record if that side is present

Occupancy and other people

Plant rooms sit under offices and kitchens. Write which side is off, where the drain lands, and that a DHW exchanger is a hygiene asset, not a radiator.

Substances and COSHH

An SDS is an input, not a COSHH assessment. If these substances appear on the job, attach assessments that describe quantity, duration, who is exposed and the controls you will actually use:

  • Primary and secondary fluids (name LTHW, CHW or DHW)
  • Gasket lubricant if specified
  • CIP acid or caustic if used

How SafeForJob helps

  • Describe this job in plain English and get suggested activities, risks and method steps
  • Edit every line before you download or issue
  • Reuse a previous RAMS and catch old client or site names
  • Attach or create COSHH assessments where hazardous substances appear

What this page is not

This page is not HSE approval, legal advice or a substitute for competent judgement. It helps you draft a clearer plate heat exchanger rams document for a named job. You remain responsible for reviewing and issuing it.

Related reading

See what a RAMS is, the free RAMS generator, and HSE guidance on managing risks.

Related pages

All rams by job · RAMS by trade · Free RAMS generator

Questions

Is this the same as a calorifier?
No — a PHE has no store but two live circuits and a plate pack.
Can I mix plates from the heating PHE?
No. Duties and gaskets differ.
Is the CIP SDS enough?
No. SDS ≠ COSHH — write dilution, time and who is exposed.
Who witnesses the DHW restart?
The dutyholder for the written scheme — name them.