Skip to content
SafeForJob

RAMS by job · UK

Microwave dish RAMS

This is not a rooftop macro cell RAMS. This job covers mounting a microwave dish on a live rooftop or mast, and the control that keeps people safe is RF/access lock-off and a lift plan before anyone leaves the ground. If the RAMS never names the drop zone, weather and who walks the roof, a principal contractor will send it back.

Typical scope

  • RF/access lock-off and a lift plan before anyone leaves the ground as a hold point
  • The drop zone, weather and who walks the roof named
  • Exclusion that actually holds
  • Sequence that cannot skip the critical control
  • Handover of residual hazards
  • Review before issue — not a stamp

Quick answer

A microwave dish rams covers mounting a microwave dish on a live rooftop or mast on a named UK site. The critical control is RF/access lock-off and a lift plan before anyone leaves the ground. Write the drop zone, weather and who walks the roof into the sequence — a pack that could describe any rooftop macro cell RAMS will not survive a competent review.

Primary topic: microwave dish rams. UK contractors — review every document before you issue it. SafeForJob does not replace competent judgement or HSE guidance.

What usually goes wrong

These are the operational gaps that make generic Word RAMS fail on the next site.

  • rooftop macro cell RAMS reused

    No RF/access lock-off and a lift plan before anyone leaves the ground.

  • Critical control buried

    The drop zone, weather and who walks the roof belongs in the sequence.

  • Occupancy ignored

    The drop zone, weather and who walks the roof and that someone who did not read the pack will walk the exclusion.

Example

Microwave dish on a named site

Built from one job description. You review and adjust every item before issuing it.

Job description

Mounting a microwave dish on a live rooftop or mast at North aisle, Frome Minster, Frome. Midweek shutdown 09:00–16:00. RF/access lock-off and a lift plan before anyone leaves the ground; the drop zone, weather and who walks the roof; the drop zone, weather and who walks the roof and that someone who did not read the pack will walk the exclusion.

Activities identified

  • General site work
  • Roof work
  • Electrical isolation

Method (9 steps)

  1. 1.Arrive and sign in. Arrive at North aisle, Frome Minster, Frome, report to the Frome Minster Estates site contact, sign in and complete any site induction.
  2. 2.Brief the team. Brief all operatives on this RAMS, the COSHH assessments and the emergency arrangements. Record attendance.
  3. 3.Set up exclusion zone below. Establish an exclusion zone below the work area with barriers and signage before any work at height starts.
  4. 4.Isolate the electrical supply. Identify the relevant circuit, isolate, lock off and tag. Prove dead with an approved voltage indicator, proved before and after use.
  5. 5.Access the roof. Access the roof via the agreed route. Confirm edge protection is in place and identify any fragile areas before moving onto the roof.
  6. 6.Carry out electrical work. Carry out the electrical work on the isolated circuit to BS 7671.
  7. 7.Remove isolation and re-energise. Confirm the work is complete and everyone is clear, remove locks and re-energise.
  8. 8.Clear up and remove waste. Clear the work area, remove waste from site (including recovered refrigerant and hazardous waste) and leave the area safe.
  9. 9.Hand over and sign out. Hand over to the Frome Minster Estates site contact, report anything outstanding and sign out.

Main risks (5 in total)

Fall from roof edge

Residual Medium

Who: Operatives

  • Plan work to be done from below or from a MEWP where possible
  • Edge protection (guard rails) or parapet of adequate height in place before work starts
  • Safe access route to the roof agreed with the site; roof hatch secured open
  • Where collective protection isn't possible, use a fall-restraint system with suitable anchors
  • Work stops in high winds, ice or heavy rain

Fall through fragile roof or rooflight

Residual Medium

Who: Operatives

  • Treat all roof sheets and rooflights as fragile unless confirmed otherwise by the site
  • Rooflights covered or protected with suitable mesh or barriers
  • Staging or crawling boards used; no walking directly on sheets
  • Safety netting or fall arrest below where required

Falling objects

Residual Low

Who: People below, other trades, public

  • Exclusion zone set up below the work area with barriers and signage
  • Tools tethered when working at height; materials kept away from edges
  • Banksman or second person controls the area during lifts and removals
  • Hard hats worn in the exclusion zone

Adverse weather

Residual Low

Who: Operatives

  • Forecast checked before work; work at height stopped in high winds
  • Breaks, water and shade in hot weather; warm clothing in cold
  • Sun protection on exposed work in summer

+ 1 more risks in the full RAMS.

What to get right on this document

Critical control first

Put this hold point first: RF/access lock-off and a lift plan before anyone leaves the ground.

Name the site facts

The drop zone, weather and who walks the roof

People who did not read the pack

The named site stays in use around this microwave dish job

What this document has to cover

This is not a rooftop macro cell RAMS. This job covers mounting a microwave dish on a live rooftop or mast, and the control that keeps people safe is RF/access lock-off and a lift plan before anyone leaves the ground. If the RAMS never names the drop zone, weather and who walks the roof, a principal contractor will send it back.

A microwave dish rams only holds up if it names the site, the people at risk, the critical control, and the order of work. Principal contractors reject paragraphs that could apply to any job of this type.

Typical hazards to assess on this job

  • People hurt if RF/access lock-off and a lift plan before anyone leaves the ground is skipped on this microwave dish job
  • Microwave dish left open so a passer-by reaches the hazard
  • Wrong isolation so a sister microwave dish stays live
  • Manual handling or dropped parts on this microwave dish job
  • Weather, dust or a substance unique to mounting a microwave dish on a live rooftop or mast
  • The next crew inheriting an open microwave dish hazard because handover was a text to nobody

Likelihood and severity change with occupancy, access, weather and other trades. Copying last month’s scores without looking at this site is how people get hurt.

A method sequence that actually protects people

Write the sequence so the critical control cannot be skipped. If isolation, edge protection or service location is the difference between safe and unsafe, it belongs before the work step — not in a general ‘PPE will be worn’ line.

  • Hold point: RF/access lock-off and a lift plan before anyone leaves the ground
  • Brief the dutyholder on the drop zone, weather and who walks the roof
  • Set an exclusion that matches rooftop macro cell RAMS failing on this site
  • Do the work to the sequence that keeps RF/access lock-off and a lift plan before anyone leaves the ground first
  • Test or prove the critical control still holds
  • Handover residual microwave dish hazards in writing

Occupancy and other people

The named site stays in use around this microwave dish job. Write the drop zone, weather and who walks the roof and that someone who did not read the pack will walk the exclusion as occupancy control, not a hope.

Substances and COSHH

An SDS is an input, not a COSHH assessment. If these substances appear on the job, attach assessments that describe quantity, duration, who is exposed and the controls you will actually use:

  • Substances used while mounting a microwave dish on a live rooftop or mast
  • Cleaning wipes specified for the finish
  • Dust or residue from the opened plant

How SafeForJob helps

  • Describe this job in plain English and get suggested activities, risks and method steps
  • Edit every line before you download or issue
  • Reuse a previous RAMS and catch old client or site names
  • Attach or create COSHH assessments where hazardous substances appear

What this page is not

This page is not HSE approval, legal advice or a substitute for competent judgement. It helps you draft a clearer microwave dish rams document for a named job. You remain responsible for reviewing and issuing it.

Related reading

See what a RAMS is, the free RAMS generator, and HSE guidance on managing risks.

Related pages

All rams by job · RAMS by trade · Free RAMS generator

Questions

Is this the same as a rooftop macro cell RAMS?
No. A microwave dish RAMS has to name the drop zone, weather and who walks the roof. A rooftop macro cell RAMS will not survive a competent review.
Can we skip RF/access lock-off and a lift plan before anyone leaves the ground?
No. RF/access lock-off and a lift plan before anyone leaves the ground is the hold point. Write it before the work step.
Who writes the drop zone, weather and who walks the roof?
The competent person who issues this microwave dish rams. A sticky note is not a handover.
Can AI issue this microwave dish rams?
A tool can draft a microwave dish pack. A competent person reviews and issues it for this site.